Author: Jesse

Capacitors

Capacitors

There are two types of capacitors you’ll encounter in HVAC field. We have the run capacitor and the start capacitor. Both are measured in microfarads which you will see labeled as uf, µF, or mfd.

Capacitors are used only in single-phase motors. You will not see a capacitor in a three-phase unit.

Run Capacitor

Max applied voltage is the maximum back emf that can be applied to the capacitor before the dielectric fluid inside the capacitor will break down. We use 370V and 440V. When you’re replacing a 370V, you can use either a 370V or a 440V since the 440V is a higher rated. You cannot use a 370V in place of a 440V since the 370V is a lower rating. You can only use a higher rated capacitor (440V) in place of a lower rated capacitor (370V).

When you measure across a capacitor with a multimeter, you will see a higher voltage than your applied voltage. That’s because you will also be measuring the back emf from the Start (secondary/auxiliary) winding.

Run capacitors are designed to be cooled by air passing over the body and filled with oil. The temperature limit is written on the label.

Dual Capacitor

We also use dual run capacitors which is just two capacitors in one. You will run into these quite a bit when working on condensers in air conditioning.

Dual run capacitor terminals:

  • Herm – Hermetically sealed compressor. That’s the auxiliary winding of the compressor and the higher of the listed microfarad rating. So in the 45/5uf capacitor above, it’s the 45uf
  • Fan – Fan of the condenser and the lower of the two ratings. In the 45/5uf rating, it’s the 5uf
  • C – Common point of the capacitor

The weak point is designed to give away if the capacitor overheats. It’s an intended weakness for safety.

Sometimes your capacitor will be so rusted you cannot make out the terminal labels. In that case, Common will usually have 4 terminal taps, Herm will have 3 terminal taps, and Fan will have 1 or two terminal taps.

It’s a common misconception that a run capacitor is used to boost voltage in a motor or that current will flow through a capacitor. While capacitors like that exist, we do not use them in a PSC (permanent split capacitor) motor.

A run capacitor is used to power the secondary winding of a motor in a single-phase application bringing that secondary winding back in phase with the run winding. This secondary winding can also be referred to as the auxiliary winding. In most residential heating and air conditioning, this would be the Start winding of the motor whereas the Run winding would be the primary winding.

If you recall from the, “What is Alternating Current” lesson, electrons reverse 60 times a second and are labeled as positive and negative on the sine wave. This shift is essential in understanding capacitors.

We’re going to be focusing on a compressor in a condenser using for electrical flow in this lesson.

  • T1 of the contactor feeds through Common of the compressor, through Start (secondary/auxiliary) winding to Herm on the capacitor. That charges the Herm side of the capacitor. You can think of it as the electrons are just sitting on that terminal waiting to discharge backward and power the secondary winding
  • Meanwhile, T2 of the contactor feeds to Common on the capacitor. Remember, this Common terminal on the capacitor is not connected to anything aside from T2
  • Once we have a sign wave shift, electron flow reverses causing the capacitor to discharge back the way they came. So, the electrons that are stored on the Herm terminal reverse, flowing from Herm on the capacitor, through the secondary (start or auxiliary) winding of the compressor powering it

At no point does any current move through the capacitor. It only stores and discharges on the Herm and Fan side, although we’re just focusing on the Herm side now.

Start Capacitor

Start capacitors are used in conjunction with a potential relay (start relay). A start relay is left in the circuit until the motor reaches about 3/4 of the running speed. It happens in about a second or less. It has to be taken out of the circuit because they’re increasing torque much more than a run capacitor. The capacitor could explode or destroy the windings in the compressor if left in the circuit.

The start capacitor is used to increase the phase angle between the secondary (start or auxiliary) winding and the run (primary) winding.

Start capacitors are rated with a range, such as 189-227uf, which is quite a bit higher than a run capacitor.

Potential relay

Potential relay

The potential relay is used in all capacitor start/capacitor run motors. They’re also used in capacitor start/induction run motors. However, it’s rare to see that style of a motor in residential and lite commercial in our industry.

The potential relay may also be called a start relay. Without it, the start capacitor could explode or destroy the windings in the motor within seconds. Using a start capacitor with a potential relay is known as a hard start kit.

Schematic layout of the relay above

With the metal rotor turning and surrounded by motor windings, this generates a significant voltage called back emf. As back emf is generated across the start winding, a small current will flow through the start winding and across the coil of the potential relay. With this happening, the potential relay takes the start capacitor out of the circuit using this back emf when the motor reaches about 3/4 of its speed.

With power removed from the motor, the back emf generating across the start winding of the motor will become too low and the contacts that were opened will again close.

The potential relay has a coil wired between terminals 2 and 5 and NC (normally closed) contacts between terminals 1, and 2. 4 and 6 are dummy/ convenience terminals.

Testing the relay

Checking a potential relay is quite simple as there’s not much to them.

Coil – Between terminals 2 and 5

The coil of the relay is between terminals 2 and 5. It’s very high resistance, so use a high setting on your meter if it doesn’t self-adjust. You should have a reading in the thousands of ohms. I’ve typically seen them around 10kΩ – 12kΩ. OL or infinity would indicate no continuity through the coil meaning a broken wire in the coil, and this potential relay would need replacement.

NC Contacts – Between terminals 1 and 2

With power off to the appliance, disconnect the wires on terminals 1 and 2. Using an Ohm meter, check resistance across the two terminals. You should read near 0Ω or very very close. While set to continuity with the beep, you should hear the beep sound indicating the contacts are closed.

If you read OL or infinity, that means the NC contacts are not open. They would be stuck open. You would need to replace this potential relay.

Relay and contactors

Relay and contactors

Relay

We’ll be using the most common type of relay in residential service, a 24v relay. A relay is an electronically operated switch that opens and closes using an electromagnet. The electromagnet is a coil of wire that when powered acts as a magnet to close/open a switch.

Terminal 1 of this relay is the common terminal. It’s “common” to terminal 2 and 3. Terminal 1 will be our terminal that will pass on power to and/or complete the circuit between terminal 2 or 3 when 24v is applied to the electromagnet.

Terminal 2 of the relay is a NC (normally closed) contact which you will usually see written on diagrams and equipment as NC. So when no 24v is powering this relay, the switch between terminals 1+2 is closed completing that side of the circuit.

Now when you power the coil with 24v, the switch between terminals 1+2 open and break the NC connection.

Example: If you had 120v to terminal 1 and terminal 2 was connected to a light, that light would be on as that circuit is NC. As soon as the relay is powered by 24v, the switch opens and the NC connection is now open breaking the circuit and the light goes out.

Terminal 3 of the relay is a NO (normally open) contact which you will usually see written on diagrams and equipment as NO. So when no 24v is powering this relay, the switch between terminals 1+3 is open with no completion of that circuit.

Now when you power the coil with 24v, the switch between terminals 1+3 closes and completes the NO circuit making it closed allowing for power to pass.

Example: You have no 24v powering the relay. You do have 120v to terminal 1. Terminal 3 is connected to a light. So this light would be off as that circuit between 1+3 is NO. As soon as the relay is powered with 24v, the switch between 1+3 closes and the NO connection is now closed making the circuit, and the light goes on.

As you can see with a powered relay, the NO changes to NC and the NC changes to NO.

Terminals 4, 5, and 6 are controlled the same as terminals 1, 2, and 3. It just gives you the option to control another piece of equipment at the same time with one relay instead of two.

Switches

Switches

A switch opens and closes to allow the flow of electric current or to stop it. There are many types of switches including, but not limited to manual switch you would have to turn on an off, switches reacting to pressure, heat, or to water or air.

Switches are designed to be either normally open (NO) or normally closed (NC). They will either make or break a circuit.

Example: A pressure switch is designed to sense unsafe operation of a furnace. It’s a NO (normally open) switch that closes on the rated negative pressure. When exhaust venting becomes plugged, the pressure the switch senses is not correct and breaks the circuit.

Wiring in the circuit connects to the contacts of the switch to move current through the circuit when the pole comes into contact with the contacts.

SPST – Single Pole, Single Throw

The switch is either open or closed like a furnace door switch and has one pole and one contact.

SPDT – Single Pole, Double Throw

Similar to the SPST, but with an extra throw (contact). The SPDT has a pole that can move to one of two contacts

DPST – Double Pole, Single Throw

Like the SPST but with an extra pole and contact. 240v appliances are controlled with one pole wired to L1 and the other pole wired to L2 with each pole being 120v.

DPDT – Double Pole, Double Throw

Similar to the DPST, but with an extra throw and extra contact per pole.

Types of diagrams

Types of diagrams

Position diagram

The position diagram shows the location of all components and is most often not included by the manufacturer.

Schematic Diagram

Schematic diagrams are also known as ladder diagrams and are helpful when you need to see the electrical current flow. Schematics will not show the physical location of any equipment in the circuit. Schematic diagrams move from left to right. The left side is the hot or line side. Switches and loads are in the middle. Neutral or common is on the right side.

Frequently a piece of equipment will contain more than one voltage passing through it, such as a relay. The relay has 24V going to the coil, but the switching contacts (NO and NC) will have 120V. In this case, the 24V coil would be in the lower level of the schematic, and the contacts will be in the top section of the schematic. In this case, the components are labeled so the technician can identify the switching contacts the coil is powering. An example would be a relay coil labeled RC1 and the contacts labeled RC1.

Wiring Diagram

Wiring diagrams are the most useful diagrams as they show actual wiring connections between each piece of equipment throughout the circuit. These types of diagrams are beneficial if you need to rewire a circuit or trace out wires since you can see the physical location of wires. Wires run horizontal and vertical in the wiring diagram.

Some manufacturers will represent two or more wires joining with a dot at the connection point of the wires. The connection point can be useful when there are many wires to trace.

Sometimes you will see a half circle representing a wire crossing over another wire to make it clear there’s no connection made and the wire has jumped over.

Wiring diagrams place components within their general location in most cases and also use symbols that represent their likeness.

Wiring diagrams

Wiring diagrams

Wiring diagrams are used as a map to find your way through the electrical circuit. Schematic and Connection diagrams (also known as wiring diagram) are the two main types of wiring diagrams.

Using the schematic diagram, you can learn the sequence of operation if it’s an appliance you’re not sure of.

The connection diagram (also known as wiring diagram) can be used to see where each wire connects to in the appliance.

All wiring diagrams will be shown in an at-rest position. This means no power is moving throughout the circuit and the thermostat is not operating. No device in the circuit will be energized while at rest and all switches are sitting in their default NO or NC position.

Schematic Diagram Example

Wiring Diagram Example

The footer of the diagrams will contain a legend and extra information needed to follow the diagrams as well as wiring information. This can be found in the appliance installation manual as well as the back of the appliance door cover.

Flame rectification

Flame rectification

The flame sensor exists to prove a flame across the burners. Without this flame sensor, there’s a risk of releasing gas without flame and risking an explosion upon ignition. The flame sensor is positioned on the opposite end of the burners from the igniter to ensure all burners ignite correctly.

Upon a call for heat, before the burners ignite, the furnace control board will send AC voltage to the flame sensor. This amount of voltage varies from manufacturer to manufacturer, but it’s usually between 80v – 100v. This voltage goes through a wire from the control board, to the wire that connects to the flame rod. You can think of it like the electrons are building up at the tip of the flame rod just waiting for a path so they can keep moving.

Since there is no flame upon a call for heat, there’s no path between the flame rod and the burners. The board needs to confirm the safety is in working condition and reading no flame before gas is released.

If you do sense flame before ignition, you may get an error similar to, “flame sensed without gas valve energized.”

Once flames are present, the board has seconds to recognize it. You have 80 – 100v AC from the board to the flame sensor. This current can travel from the flame rod through the flame due to flame ionization. The flame bridges the gap between the burners and the flame rod.

When we burned fuel, it releases electrons from the molecules in the fuel, and this lets the flame act as a path for current to move from the rod, through the flame, and to the burners grounding surface. Since the furnace burners have a much larger surface area than the flame rod, the current cannot backtrack to the rod and is rectified (hence the name flame rectification) to DC (direct current) which only travels in the one direction.

You measure the flow of current passing through the flame sensor in DC microamps. The control board will monitor the DC microamp through a ground wire usually located on the burners, back panel, or on the gas valve. You’re commonly looking for a reading of between 1 – 4 microamps.

Even without a call for heat, the board is still checking the flame sensor for safety at all times, so you will always have voltage present at this sensor.

If your appliance is failing on flame signal, here’s a few things to check:

  • Clean any buildup on the flame sensor. As this flame sensor sits in the flame, it becomes dirty with oxidation or carbon buildup. You can clean this with a piece of sandcloth but take it easy on it. The flame sensor doesn’t need to sparkle
  • Ensure your ceramic insulator is not cracked causing the AC voltage to bypass the flame sensor and go to ground without rectification
  • Check to make sure your grounds are secured, clean, and you have a proper 120v dedicated ground
  • Check to make sure you have the correct polarity of 120v hot and neutral
  • Check to see if the flame sensor is sitting in the flame correctly
  • Check to make sure gas pressure is suitable for the unit
  • Check to see if you have AC voltage going to the flame sensor or that is correct. You may need to call technical support for this

How to measure flame rectification

  1. With the appliance off, connect your multimeter in series with the flame sensor. In series means you are making a connection point in line with the flame rod. Disconnect the wiring lead from the flame sensor. Connect one side of your meter leads with an alligator clip to the flame sensor. Connect your other multimeter lead to the wire removed from the flame sensor. The other end of that wire connects to the control board or ignition board
  2. Make sure your multimeter is set to microamps
Back EMF and impedance

Back EMF and impedance

When passing an alternating current through a coil of wire, like a transformer or a solenoid valve, the expanding and collapsing magnetic field created by the alternating current induces a back-voltage (back EMF) in the coil which goes against the supply voltage. All coils of wire will have this.

If you have two sets of windings near one another, you can “induce” a voltage from one to the other. A transformer has two sets of windings. The primary and secondary windings. One coil (primary winding) is connected to alternating current, and the expanding and collapsing magnetic field from that coil will “induce” a voltage in the nearby coil (secondary winding). The voltage produced is in the opposite direction, opposing the original voltage.

Inductive reactance is a form of resistance that only exists when an alternating current is present due to frequency. Higher the frequency, lower the current due to higher resistance. It cannot be measured with an ohmmeter or Ohm’s Law. You’ll have to use the power factor multiplier for the piece of equipment.

The total resistance of a circuit containing a coil is called the impedance. It’s the sum of the measurable Ohm’s Law resistance you measure with no power applied, and the resistance due to the inductive reactance.

Solenoid

Solenoid

Solenoids operate on the principle of electromagnetism. With current moving through a conductor, a magnetic field forms around the conductor. A single straight conductor by itself will not generate a strong magnetic field, but if the conductor is wound into a tight coil, it will produce a strong magnetic field. Each loop of the coil will create a small magnetic field, and every loop combines to create a larger magnetic field. The more wound loops, the larger the magnetic field produced.

Adding an iron bar inside the coil of wire will create a solenoid. When the circuit is complete with the switch closed, the magnetic field generated will pull the iron bar to the center of the coil. This form of electromagnetism is used with relays and gas valves.

With a closed circuit, current flows through each loop of the wound coil. Each wound loop creates a small individual magnetic field, which when totaled together loop adds up to a much larger magnetic field.

The armature is pulled into the middle of the coil with the generated magnetic field moving the seat up.

Once the circuit is open, and no current is flowing, the armature is released back to its resting position.

Ground fault circuit interrupter (GFCI)

Ground fault circuit interrupter (GFCI)

A GFCI is not the same as a breaker or fuse. It exists to protect people whereas a fuse or breaker exists to protect the conductors in your house. A GFCI works on the principle that the current moving through a circuit should be the same at all points of the circuit. The GFIC monitors current going from hot to neutral. If the current going from hot differs from neutral, the GFIC trips and stops the flow of current.

The GFCI receptacle believes that if there’s an imbalance between the two currents, hot and neutral, there’s a chance the current could be going through you. The GFCI will trip on as low as 4 or 5 milliamps and in about 1/30th of a second. It takes about 30 milliamps to kill a person.

Example: You’re drilling a hole through a wall outside. It’s a bit wet out, so this provides a perfect path to ground for current if anything goes wrong. There’s an open hot wire inside the drill to the casing. If current goes from hot, through the drill, through you to ground, the GFCI will sense an imbalance from hot to neutral and stop the flow of current.

GFCI receptacles are usually mandatory in kitchens, bathrooms, outside, garages and anywhere around water, but you’ll need to check local building codes to be sure.

GFCI protection also is available with GFCI circuit breakers and GFCI cords (like an extension cord).