Earlier we covered electrons moving from atom to atom. Metallic bonding forms copper. The bond is made when many metal atoms share their collected valence electrons. The valence electrons are not attached to any specific atom, so they move around freely.
Now to get these electrons moving in one direction and being of more use, they just need a push. This is by applying an electromotive force (emf), also known as voltage.
Voltage can be compared to the pressure water is forced out of your kitchen faucet. It would be the water pressure that caused the water to flow.
When you measure voltage, you measure the potential difference between two points in a circuit. It’s important to remember this because you may measure 0 volts and take a good shock if you touch that wire.
In Ohm’s Law, voltage is represented by “E.”

What this means on a service call
Voltage tells you whether the push is present at the point you are testing. It does not tell you whether a load is good. It does not tell you how much current is flowing. On a service call, start with that simple question. Is voltage reaching the part that should run, or is it stopping at a switch, a control, or a broken wire before it? Do not jump to the load until you know the push reached it.
Keep the control side and the line side separate in your mind. The control circuit, often 24V, tells the system what to do. The line circuit, often 120V, supplies the power for a motor, a fan, or a heater. A system can have control voltage and still have no line voltage at a load. It can also have line voltage present and still not run because the control signal never arrived. Test each side on its own. Record the two points you used and the reading.
A dead load with voltage upstream is a different fault from a dead load with no voltage upstream. The first points to the load or the path after your last good reading. The second points to the supply, a control, or a wire before it. Say which case you have before you change a part. That one sentence, written on the job notes, will save a second visit.
Numbers and measurements you will see
Compare every reading with the wiring diagram, the nameplate, or the manual for the unit in front of you. The examples below show what to look for. They are not a pass mark for every unit.
- 24V control. Expect 24V between the control terminals when the control should be on. If you read 0V there, the signal is missing, a switch is open, or a wire is broken upstream.
- 120V line. Expect 120V at the line side of a disconnect or at a load that should be running. If it is present at the input and missing at the output, the break is between those points.
- 0 volts. A 0 volt reading can mean no power, an open switch, or two points at the same potential. It does not prove a circuit is safe to touch.
- Voltage across a switch. Full applied voltage across an open switch can be normal. The push is reaching that point and stopping there. Full voltage across a closed switch points to a bad connection or an open contact.
- Flame sensor example. The 80 to 100V range already used on this site for a flame sensor belongs to that one test. Do not apply that range to other parts.
- Series check. In the series example on this site, 6V plus 6V adds to 12V. In a series circuit, the drops across the parts should add up to the applied voltage.
A load that is running should have voltage across it. A wire or a closed switch should have little voltage across it. If a wire shows a large drop, check the connection at each end. Do not keep running a circuit with a hot connection. Find the cause first.
A common mistake
The most common mistake is to read 0 volts, call the circuit dead, and touch a wire. The original post warns about that exact error. A meter only reports the difference between its two leads. If both leads touch points at the same potential, the meter reads 0 volts even though both points are live to ground. A loose lead, a painted surface, or a corroded terminal can also give a false 0. Seat both leads, clean the test point if needed, and watch the reading while you hold them steady.
A second mistake is to replace a part because voltage is present at its terminals. Voltage present means the push arrived. It does not prove the part can carry current or do work. Check current and resistance, where the test is safe and the power state is right for that test, before you condemn the part.
Check it in the field
- Set the meter for the right kind of voltage and a range that covers the circuit. Check the leads for damage. Test the meter on a known live source, test the circuit, then test the meter again. If it does not read as expected on the known source, stop.
- Pick two test points from the diagram. Put one lead on each point, keep your hands clear of bare metal, and record the reading and the points.
- Move one lead at a time along the circuit. When the reading changes, you have crossed the point where voltage is lost. That narrows the fault to one section.
- Do not bypass a safety control to get a reading. If a control is open, find why it is open.
Voltage testing is a live test. Treat every conductor as live until you have proved otherwise with a meter you trust. Keep leads and hands away from other bare parts. Use a meter rated for the circuit. If you are unsure, stop and get help.
Related posts
These posts belong together. Use the summary for the short version, then work through each part on its own.
- Voltage, current, and resistance summary: a short recap of voltage, current, and resistance together.
- Current (amps): what flow means, and how to check it without guessing.
- Resistance: what opposition to flow means, and why a load must have resistance.
- Series Circuits: one path for current, and how voltage drops add up.
- Parallel Circuits: more than one path, and why one branch can fail while others keep working.
- Ohm’s Law: how voltage, current, and resistance relate, with worked examples.
