Resistance

Almost all material has some form of resistance to electrical flow. Without resistance, you’d have no way for a circuit to do useful work. Like stated earlier, conductors are materials that allow current to flow, and insulators don’t. Conductors have little resistance.

Resistance in a circuit is measured in Ohms or the Greek letter “Ω.” Current flowing through an electric range or toaster causes the elements to generate heat to cook your food by using resistance. In Ohm’s Law, resistance is represented by “R.”

All good loads, like a motor or light, will have some form of measurable resistance otherwise current would easily pass through the load without completing any useful work like lighting up the room or moving air throughout your house.

Example: Water flowing through a garden hose without a kink has less resistance and allows water to flow at a faster rate

What this means on a service call

Resistance is what turns current into useful work. A good load has resistance you can measure. A motor, a heater, or a light does work because current meets resistance in that load. Without resistance in the load, current would pass through without doing the work you need.

Resistance also shows up where you do not want it. A loose or corroded connection adds resistance in series with the load. That added resistance makes heat, causes voltage drop, and starves the load. The load may run weak, the connection may run hot, or the load may not run at all. Check the connection before you condemn the load.

Numbers and measurements you will see

Do not use a single ohm value as a pass mark for every part. This site does not give a resistance rating for each motor, heater, or control in the cluster posts. Compare a reading with the diagram, the nameplate, or the manual for the unit in front of you. The examples below come from posts on this site, and they show how resistance fits with voltage and current.

  • 10 ohms in Ohm’s Law. In the Ohm’s Law example, 5V divided by 0.5A gives 10 ohms. If you know voltage and current, you can check whether a resistance value makes sense.
  • 10 ohms in series. In the series example, 5 ohms plus 5 ohms gives 10 ohms total. Resistance adds in series, so the total is higher than any one part.
  • 8 ohms in parallel. In the parallel example, 12 ohms and 24 ohms in parallel give 8 ohms total. Resistance in parallel is lower than any one branch.
  • OL, or open. Most meters show OL when the path is open. That means no complete path for current between the leads. An open winding, a broken wire, or an open switch can all read OL. Check the test points before you condemn the part.
  • Near 0 ohms. Touching the leads together should read near 0 ohms. A closed switch, a good wire, or a good connection should also read near 0 ohms. Near 0 ohms across a load that should have resistance can mean a short, so check what the part should read.
  • Higher than expected. A reading much higher than the value for that part can mean a poor connection, a damaged winding, or a part that is failing. Repeat the test with clean, firm lead contact, and isolate the part before you trust the number.

A common mistake

The most common mistake is to measure resistance on a live circuit. A meter in ohms mode sends its own small test current through the part. Voltage from the circuit will confuse the meter, give a false reading, and can damage the meter. Prove the circuit is dead first, with a voltage test you trust, then switch to ohms. If you are not sure the circuit is dead, do not take an ohms reading. Stop and prove it dead first.

A second mistake is to measure a part while it is still connected to the rest of the circuit. Other branches give current another path, so the meter can read lower than the part alone. The parallel rules explain why. Disconnect or isolate at least one side of the part, where the diagram and safe practice allow it, so the meter sees only the part you want to test. A third mistake is to condemn a part on one reading alone. Compare the same type of winding or the same type of part, check the leads, and repeat the test. One number, without context, is not a diagnosis.

Check it in the field

  1. Turn the power off for the circuit you will test. Prove it dead with a voltage test, using a meter you have checked on a known live source. Follow the equipment instructions if a component can hold a charge.
  2. Isolate the part. Disconnect at least one side, where safe practice allows it, so other branches do not give a parallel path.
  3. Set the meter to ohms. Touch the leads together and note the reading. It should be near 0 ohms. Hold the leads apart and note the reading. It should show OL. If either check fails, fix the meter or the leads first.
  4. Put one lead on each end of the part, with clean and firm contact. Record the reading, the meter range, and the test points. Compare it with the diagram, the nameplate, or the manual.

Do not touch the metal tips of the leads while you take a reading. Your body can give current another path and change the result. Keep hands clear, hold the insulated parts of the leads, and let the reading settle before you record it. If you are unsure about the power state, stop and get help.

Related posts

These posts belong together. Use the summary for the short version, then work through each part on its own.

Leave a Reply

Your email address will not be published. Required fields are marked *