Alternating current

What is Alternating Current?

Alternating current, (AC) is the most common form of electricity. AC became the standard due to the ease of distributing power over a long distance. With AC, a simple transformer outside your house steps the voltage down from the power company supply to a usable voltage in your home. Since it’s made up of no moving parts and some coils of wire, it’s a lot less expensive than using DC power as the standard delivery method.

In alternating current, the electrons do not move in just a single direction like they do in a DC circuit. Electrons will travel one path going from atom to atom, happy as can be, then turn around and hop backward atom to atom. They do this many times per second.

The rate at which alternating current reverses direction is called the frequency, and we express this in Hertz. Canada and the US are at 60 Hz whereas Europe is 50 Hz.

Example: It often helps compare the back and forth flow of alternating current to water in a piping system.

With the shaft fully forward, water is pushed in one direction. Water will start to move in this direction as the shaft begins to push outwards from the opposite direction.

As the shaft starts to pull in, water alternates direction and flows the opposite way. Now visualize this taking place 60 times a second.

Regardless of what direction of flow, water still flows throughout the whole piping system.

Each time the shaft in the piping above is fully outwards or fully inwards would be the peaks of the positive and negative sine wave.

What this means on a service call

Alternating current powers almost everything you touch on an HVAC call. The line circuit, the control transformer, the motors, and the controls all run on AC. When AC is missing or wrong, the equipment cannot run, even if every part is good.

AC changes direction many times per second, as the original lesson states. Your meter hides that back and forth movement and shows a steady voltage value instead. That steady value is what you use to decide if power is present. A motor that hums, a control that will not pull in, and a transformer that reads 0V all start with the same first test: is AC voltage present at the right two points.

The transformer is the link between the line circuit and the control circuit. The original lesson notes that a transformer steps voltage down from the power company supply to a usable voltage in the home. On HVAC equipment, that step down gives you the 24V control circuit. If the line side has 120V and the control side has 0V, the transformer, its fuse, or its wiring is the next place to check. If both sides are dead, the problem is further back toward the disconnect or the breaker.

Numbers and measurements you will see

Use the meter on the AC volts setting for AC work. The numbers below are the common field values from the lessons on this site.

  • 120V on a line circuit, measured at the disconnect or at the line side of a control. A reading near 120V tells you line power is present at that point.
  • 24V on a control circuit, measured from R to C on a transformer or a control board. A reading near 24V tells you the transformer secondary is powered and the control circuit has a source.
  • 0V across a closed switch or a closed contact. When a switch or a contact is closed and current can flow, there should be little or no voltage drop across it. A large reading across a closed contact points to a bad contact.
  • Full voltage across an open switch or an open contact. When a switch is open, the full circuit voltage appears across it. That reading proves power is reaching the switch, even though the load is dead.
  • 60 Hz in Canada and the US, and 50 Hz in Europe, as stated in the original lesson. A meter with a Hertz setting should show 60 Hz on a standard AC supply in Canada and the US. A reading far from 60 Hz, or no Hertz reading, tells you to recheck the meter setting and the test points.
  • 0V on a circuit that should be powered. A steady 0V reading means no difference in charge between the two test points, or the circuit is dead at that point. Work back toward the source, one test point at a time, until voltage appears.

A common mistake

Testing an AC circuit with the meter set for DC is the common mistake. The meter shows 0V or a low, unstable value, and the technician calls the circuit dead.

Line and control power on HVAC equipment is AC. Set the meter to AC volts before you test a line or control circuit. Recheck the setting if a reading does not match what the circuit should have. A wrong setting wastes time and can lead to a good part being replaced.

A second mistake is testing only one side of a circuit. A reading of 120V at the disconnect does not prove 120V is reaching the load, and a reading of 24V at the transformer does not prove 24V is reaching the thermostat. Test at the load, at the control, and at the source, and compare the three readings.

Check it in the field

Caution: live and powered work can hurt you. Treat a circuit as live until you prove it is dead with your meter. Keep your hands clear of bare conductors and terminals. If you are not sure a test is safe, stop, turn the power off, and get help. Do not bypass a switch or a safety control to force a load to run.

  1. Set the meter to AC volts. Check the meter on a known source first, such as a 120V outlet, so you know the meter and the leads are working.
  2. Test line voltage at the disconnect. Expect about 120V on a 120V circuit. If the reading is 0V, check the disconnect, the breaker, and the supply before you test further into the equipment.
  3. Test control voltage at the transformer. Measure R to C and expect about 24V. If the line side is powered and the control side is 0V, check the transformer and any fuse in the control circuit.
  4. Test across the load with the circuit calling for that load. A load that has full voltage across it and does not run has a load fault or an open inside the load. A load with 0V across it is not being fed.
  5. Test across each switch and contact in that circuit. An open switch should show full voltage across it. A closed switch should show about 0V across it.
  6. If the meter has a Hertz setting, check the frequency on the AC supply. Expect 60 Hz in Canada and the US. A reading far from 60 Hz tells you to recheck the setting and the test points.

Related posts

Leave a Reply

Your email address will not be published. Required fields are marked *